Characteristics:
This switch product is developed and improved basic on other compound switch. General compound in the magnetic switch is running the relay contactors, and the magnetic switch is design for billing meter, are usually only action several times a month. It just can use 50,000 times. Capacitance compensation generally have dozens of switching every day, the general operation of the switch a few months after magnetic relay, it is easy to fault, and have contactors stuck and switches burning.
This switch uses the two-way TSC to input the capacitor under the zero voltage, and then diverted to private-run capacitor contactor, thus, no surge when input capacitance, no running fever. The contactor design life is 60 million, thus longer life expectancy, fewer failures. After a year of operation compare, we find this switch is more stability than the composite, and low failure rate.
Technical parameters
|
1、Input Surge |
<3In |
|
2、Capacitance switching interval |
>1秒 |
|
3、Switching to repeat the same group interval |
>60秒 |
|
4、Control Voltage |
12V DC |
|
5、Control Current |
40mA |
|
6、Temperature |
-20℃~55℃ |
|
7、Relative Humidity |
40℃ 20%~90% |
|
8、atmospheric pressure |
80-106kpa(<2500m) |
|
9、Power |
Ac380V,50HZ; 或Ac430V,50HZ两种 |
|
10、Harmonic Current |
<10%In |
|
11、Life |
600000 times |
Style
|
Model |
Voltage |
Current |
Capacitance |
Size mm |
Install Way |
|
YBYWRF-30 |
380V AC |
60A |
30Kvar |
110*70*152 |
M5 bolts or 75 mm installed orbit |
|
YBYWRF-20 |
380V AC |
40A |
20Kvar |
110*70*152 |
M5 bolts or 75 mm installed orbit |
|
YBYWRF-30H |
430V AC |
60A |
30Kvar |
110*70*152 |
M5 bolts or 75 mm installed orbit |
|
YBYWRF-20H |
430V AC |
40A |
20Kvar |
110*70*152 |
M5 bolts or 75 mm installed orbit |
|